Home
Support
Contact Us
Latest News
Site Index
end.gif - 426 Bytes
Lnav_top.gif - 268 Bytes
VD2000 Series Temperature Controllers
VT10 Series Temperature Controllers
VT20 Series Temperature Controllers
VT30 Series Temperature Controllers
Self-Contained Single & Dual Zone Controllers
Heat Seal PCB
Thermostats
Custom Control Systems
SD600 Indicator
Lnav_bot.gif - 146 Bytes

Click Here For DIN Controller Comparison Chart

VD2000 Series Temperature Controllers

VD2004

The '2000' Series of low cost digital temperature controllers is designed to provide the high level of accuracy associated with digital controllers in a format that is as easy to use as analogue units, at a more competitive price.

An auxillary output is provided as standard, with 6 different alarm modes of operation and two timer modes. A parameter lock provides various levels of keyboard lockout from full access to access of only the Setpoint.

The shallow depth of the '2000' Series allows them to be used in applications that have minimal space behind the mounting panel.

All the '2000' Series controllers are now available for operation from a 24V supply for intrinsically safe control panels.

The 2000 has recently been upgrade and now includes the following additional features:-

  • Up to 3 independant alarms.
  • Simplified sensor and range setting.
  • Improved control accuracy.
  • RS485 digital communications.
VD2004 VD2003 VD2000

VD2004

VD2003

VD2000

Size: 96 x 96 x 90mm

Size: 96 x 48 x 90mm

Size: 48 x 48 x 106mm

Technical Specification

Value

Input / Display

Accuracy

Thermocouple = ± 1oC, PRT = ± 0.2oC

CJC

0.1oC / oC ambient

Update Time

500 mS

Noise Rejection

120dB

Input Types

The '2000' series controllers are supplied pre-configured to type 'J' thermocouple. Changing to another thermocouple or PRT input is simply accomplished by following information supplied in the accompanying operating manual.

Please contact the factory for available linear inputs.

Input Type

Range (C)

Range (F)

J

-50 to 1000

-58 to 1832

K

-50 to 1370

-58 to 2498

T

-270 to 400

-454 to 752

E

-50 to 1000

-58 to 1832

B

0 to 1800

32 to 3272

R

-50 to 1750

-58 to 3182

S

-50 to 1750

-58 to 3182

N

-50 to 1750

-58 to 2372

C

-50 to 1800

-58 to 3272

DIN PRT 100

-200 to 850

-328 to 1652

JIS PRT 100

-200 to 600

-328 to 1112

Linear

-1999 to 9999

-1999 to 9999

Display Range

Software selectable from preset table of ranges

Case Sealing

IP63

Output

Display

4 digit, high brightness, red LED's

Output Relay

10A @ 240V ac into a resistive load. A 3A maximum is recommended for inductive loads. (1 x 10e7 Operations)

Output Logic

24V On, less than 4V Off (100mA Max). Suitable for driving most types of Solid State Relay (SSR).

Alarm Relay

10A @ 240V ac into a resistive load. A 3A maximum is recommended for inductive loads. (1 x 10e7 Operations)

Power

Power Usage

Less than 3VA

Power Supply

90 - 264V ac, 50/60 Hz, 18 - 32V ac/dc 50/60Hz

Operating Temperature

0 to +50oC

Product Codes

The codes given below are for standard items kept in stock. Please contact the factory for any controllers required with linear inputs.

Please add '-24V' to any code for controllers that are required to run from 24V. e.g. VD2000-RELAY-24V.

Product Code

Controller

Input Type

Heat O/P Type

VD2000-LOGIC

VD2000

Thermocouple

Logic

VD2000-RELAY

VD2000

Thermocouple

Relay

VD2003-LOGIC

VD2003

Thermocouple

Logic

VD2003-RELAY

VD2003

Thermocouple

Relay

VD2004-LOGIC

VD2004

Thermocouple

Logic

VD2004-RELAY

VD2004

Thermocouple

Relay



Top - Home - Contact Us